                            ET / KS 98 and ET / KS 98plus 
							 
                             
							 
							
							Testing the interface 
							 
							
                            通讯端口检测
							 
							
							If problems arise during communication between the 
							Engineering Tool and the KS 98, it is best to check the interface first.  
							This can be done best with an "empty" engineering that contains no 
							function blocks, and is generated in the ET / KS 98 with the menu item 
							"File - New". Subsequently, the empty engineering is transmitted by 
							means of the menu item "File - Project PC -> KS98 - Engineering". 
							The transmission is completed within a few seconds, and if successful, it is 
							confirmed by the message "No fault found...".  
							Should a problem arise during transmission, the cable between the devices 
							should be checked first, followed by the interface settings, the selected COM 
							port, transmission speed, and the address.  
							Of course, this test also works with the Simulation Tool SIM / KS 98. 
							 
							
							 
							   
							 