                            SIM / KS 94 and SIM / KS 98 
							 
                             
							 
							
							Standard signals at the inputs 
							 
							
                            标准信号输入
							 
							
							The analog inputs of the simulations normally 
							expect a technical value. With thermocouple inputs, the entry "458" 
							represents a temperature of 458 0 C. If the input is configured as a
							 standard signal, a technical value is also expected. However, it is also 
							possible to simulate a current signal, in order to check the selected scaling 
							range. For this, the entered value must be preceded by '#'. 
							 
							
							Example:  
							The input is configured for 4...20 mA, with x0=200, x100=800. 
							 
							
							Entered value: #4  
							The value 4 mA is converted to 200, according to the scaling. 
							 
							
							Entered value: #20  
							The value 20 mA is converted to 800, according to the scaling. 
							 
							
							 
							   
							 